- Westermo Teleindustri Ab Modems Driver License
- Westermo Teleindustri Ab Modems Driver Updater
- Westermo Teleindustri Ab Modems Driver Ed
Westermo Teleindustri AB T05-0194 Declaration of conformity Org.nr/ Postadress/Postal address Tel. Telefax Postgiro Bankgiro Corp. Identity number Registered office S-640 40 Stora Sundby 016-428000 016-428001 52 72 79-4 5671-5550 5 Eskilstuna Sweden Int+0 Int+1 The manufacturer Westermo Teleindustri AB. The Industrial Control Modem, manufactured by Westermo Teleindustri AB and sold by H. Engineering has an Authorization Number of KCC-REM-Hse-ODW-600 Series and was approved on 2012-03-16 under application number 00005584. Westermo lonworks TP/FT (twisted pair / free topology) products can be configured as bus loop or star in one entire network. The lonworks covers fibre optic repeaters. The lonworks routers allows high data rate over long distances. A lonworks router can be installed as repeater, configured router and learning router. A lonworks repeater is.


WESTERMO TELEINDUSTRI AB
TD-23 AC

Westermo Teleindustri Ab Modems Driver License
Card Type | Modem |
Chip Set | Unidentified |
I/O Options | 9-pin serial port (RS-232), terminal blocks (3) |
Data Modulation Protocol | ITU-T V.11, V.23, V.24/V.28 |
Wiring Type | Unshielded twisted pair |
Maximum Transfer Rate | 1200bps |
Data Bus | External |
CONNECTIONS | ||||||
Function | Label | Function | Label | |||
Relay connector (screws 1 & 2) | CN1 | AC power connector (3 pole terminal block) | CN4 | |||
RS-232-C/V.24 interface (screws 3 - 5) | CN2 | Line connector (4 pole terminal block) | CN5 | |||
RS-422/485 interface (screws 6 - 9) | CN3 | 9-pin serial port | CN6 | |||
Note: CN1, CN2, & CN3 are separate interfaces on a 9 pole terminal block | ||||||
USER CONFIGURABLE SETTINGS | ||
Setting | Label | Position |
í 2-wire mode enabled (line side) | S2/6 | On |
4-wire mode enabled enabled (line side) | S2/6 | Off |
í 23ms RTS/CTS delay enabled | S2/9 | Off |
60ms RTS/CTS delay enabled | S2/9 | On |
í Activity timer disabled | S3/7 | Off |
1min activity timer enabled | S3/7 | On |
í Filter enabled; receive data is buffered for 6ms | S3/8 | On |
Filter disabled | S3/8 | Off |
LINE TERMINATION | ||
Setting | S1/1 | S1/2 |
í Line termination disabled | Off | Off |
Line termination enabled | On | On |

TRANSMISSION LEVEL | |||
Setting | S2/1 | S2/2 | S2/3 |
3dBm | Off | Off | Off |
-3dBm | On | Off | Off |
-6dBm | Off | On | Off |
í -9dBm | On | On | Off |
-10dBm | Off | Off | On |
-12dBm | On | Off | On |
-13dBm | Off | On | On |
-15dBm | On | On | On |
DCD DETECTION LEVEL | ||
Setting | S2/4 | S2/5 |
í 3dBm | Off | On |
10dBm | On | On |
-3dBm | On | Off |
-15dBm | Off | Off |
Westermo Teleindustri Ab Modems Driver Updater
CARRIER CONTROL | ||
Setting | S2/7 | S2/8 |
í Carrier controlled by RTS | On | On |
Transmitter activated by incoming data; data is buffered while carrier is established | Off | On |
Permanent carrier established | On | Off |
2-WIRE/4-WIRE MODE SELECTION (RS-422/485 SIDE) | ||
Setting | S3/1 | S3/2 |
í 2-wire mode enabled | On | Off |
4-wire mode enabled enabled | Off | On |
RS-422/485 TERMINATION | ||||
Setting | S3/3 | S3/4 | S3/5 | S3/6 |
í RS-422/485 termination disabled | Off | Off | Off | Off |
2-wire termination enabled (RS-485) | On | On | Off | Off |
4-wire termination enabled (RS-422) | Off | Off | On | On |
DIAGNOSTIC LED(S) | |||
LED | Color | Status | Condition |
PWR | Unidentified | On | Power is on |
PWR | Unidentified | Off | Power is off |
RD | Unidentified | On | Modem is receiving data |
RD | Unidentified | Off | Modem is not receiving data |
TD | Unidentified | On | Modem is transmitting data |
TD | Unidentified | Off | Modem is not transmitting data |
RTS | Unidentified | On | RTS signal is high |
RTS | Unidentified | Off | RTS signal is low |
CTS | Unidentified | On | CTS signal is high. Device ready to send data |
CTS | Unidentified | Off | CTS signal is low |
DCD | Unidentified | On | Data carrier present |
DCD | Unidentified | Off | Data carrier not present. Connection not established |
Westermo Teleindustri Ab Modems Driver Ed
Westermo is a registered trademark of Westermo Network Technologies AB, a Beijer Group company, in the United States and/or other countries.
While we have made every attempt to ensure that the information contained in this site has been obtained from reliable sources, Gross Automation is not responsible for any errors or omissions, or for the results obtained from the use of this information. All information in this site is provided 'as is', with no guarantee of completeness, accuracy, timeliness or of the results obtained from the use of this information, and without warranty of any kind, express or implied, including, but not limited to warranties of performance, merchantability and fitness for a particular purpose. In no event will Gross Automation, its related partnerships or corporations, or the partners, agents or employees thereof be liable to you or anyone else for any decision made or action taken in reliance on the information in this Site or for any consequential, special or similar damages, even if advised of the possibility of such damages.